Return to site

Plc-5 2 Slot Addressing

broken image


PLC-5 Controllers The PLC-5 family has been around since 1986 and was Rockwell's flagship PLC system until the late 90's. The PLC-5 is a powerful controller housed in a heavy-duty metal enclosure. It has built-in communication adapters on the controller to allow it to communicate with remote input and output modules. Play free Queen of The Nile 2 slot machine demo game at DemoSlotMachines.com with no deposits and no download.

Before you can program any PLC system, you have to understand how the addressing is done in that particular PLC. I have included a actual screenshot from RSLogix 5000 below that shows examples of addressing in RSLogix 5000.

INSTRUCTION – RSLogix 5000's Relay Ladder Logic command language is comprised of 'instructions'. An XIC (it looks like a normally open contact –] [– ) is an instruction. A timer is an instruction. A few of the most common instructions are described below.

BIT – an address within the PLC. It can be an input, output or internal coil, among others.

2 Slot Addressing, free poker db hud configuration, places to eat in new york new york casino, california grand casino slot machines. The IEC 61131-3 programming standard refers to this channel-based addressing of I/O data points as direct addressing. A synonym for direct addressing is absolute addressing. Addressing I/O bits directly by their card, slot, and/or terminal labels may seem simple and elegant, but it becomes very cumbersome for large PLC systems and complex programs.

RUNG – A section of the PLC ladder program that terminates in an output function of some type. Just like in an electrical ladder diagram, a rung has some type of output that is turned on or turned off by the preceding entities in the rung. The first rung in a ladder program is always 0.

HARDWIRED INPUT – a physical connection to the PLC from an input device (switch or sensor, etc.).

RSLogix 5000 defines the address of the input, based on the input cards that you configure.

We'll see how this works later on, but here is an example of a hardwired input:

Local:4:I.Data.3

Here is what each part of the address means:

Local:4:I.Data.3
'Local' means that the module is connected to a controller across a backplane or with a parallel link, keeping the module within a few inches of the controller.

Local:4:I.Data.3
'4' means that the module is module 4 (located in the 5th slot in the rack).

Local:4:I.Data.3
'I' means the bit is an input

Local:4:I.Data.3
'Data' indicates the type of data (this is the default for I/O)

Local:4:I.Data.3
'3' indicates that the bit is 4th input on the card (the bits start with 0).

By the way, don't get the capital 'I's' confused with ones.

So, in evaluating our example, we would describe the bit as 'Module 4, bit 3'.

Here is where some confusion comes in. Because the Rockwell numbering system starts with 0, and the processor resides in Slot 0, our example bit is actually in slot 5. Our bit 3 is actually the 4th bit. We could also describe the bit as 'Slot 5, position 4'.

You will have to learn to transpose these ways of describing a bit back and forth in your head. If you are troubleshooting a problem, and you want someone to look for a signal on our example bit, you might have to tell him to look at the 4th position on the 5th slot. That will lead him to the physical point on the PLC.

However, you need to keep in mind that the corresponding bit in your program will be labeled Local:4:I.Data.3.

It can be confusing, but you will get used to it.

HARDWIRED OUTPUT – a physical connection from the PLC to an output device (relay or pilot light, etc.)

Create your own poker table. Outputs are addressed the same way.

Local:5:O.Data.4
'Local' means that the module is connected to a controller across a backplane or with a parallel link, keeping the module within a few inches of the controller.

Plc 5 Slot Addressing

Local:5:O.Data.4
'5' means that the module is module 5 (located in the 6th slot in the rack).

Local:5:O.Data.4
'O' means the bit is an output

Plc-5 2 Slot Addressing Tool

Local:5:O.Data.4
'Data' indicates the type of data (this is the default for I/O)

Local:5:O.Data.4
'4' indicates that the bit is 5th output on the card (the bits start with 0).

INTERNAL COIL
This is a programmable bit used to simulate a relay within the PLC. The internal coil has no connection to the outside world. It does not connect to an output card. Internal coils are used to store information. The 'contacts' of this 'relay' can then be used multiple times in other parts of the program.

RSLogix 5000 has greatly simplified the process of describing an internal coil. We can simply give it a name, known as a tag.

For example, if you have an internal coil that is the result of, say, three hardwired safety gate limit switches, we could label the coil 'SafetyGatesClosed'.
Note the lack of spaces in the tag name. RSLogix 5000 does not allow spaces, or other special characters, in the tag name.

Some people use underscores, so the tag might be 'Safety_Gates_Closed'. Either way is fine; it just depends on what your company or your client prefers.

TIMER
A timer is a programmable instruction that lets you turn on or turn off bits after a preset time.

The two primary types of timers are TON for 'timer on delay' and TOF for 'timer off delay'.

Timers in RSLogix 5000 use tag names for identification.

COUNTER
A counter is a programmable instruction that lets you turn on or turn off bits after a preset count has been reached.

There are different types of counters available in the RSLogix, but the CTU (counter up) instruction covers everything we will talk about here.

Counters in RSLogix 5000 use tag names for identification.

–] [– Normally Open Contact
When used with a hardwired input, this instruction is off until there is a voltage applied to the input. The bit address then goes high, or on, and the instruction becomes 'true.' It works the same way when it has the same address as an internal coil, except that the coil must be turned on by logic in the program.

Allen-Bradley calls these normally open contacts 'XIC', or 'eXamine If Closed' instruction.

An XIC instruction can reference a hardwired input, a hardwired output, an internal coil or a timer done bit, among others.

–]/[– Normally Closed Contact
This is an inverted normally open contact.

Plc-5 2 Slot Addressing Software

When used with a hardwired input, this instruction is 'true' until there is a voltage applied to the input. It then goes low, or off, and becomes 'false.'

It also can be used with an internal coil, becoming true when the coil is off and becoming false when the coil is on.

Allen-Bradley calls these normally closed contacts 'XIO', or 'eXamine If Open' instructions.

-( )- Output Coil
When used with a hardwired output, this function is off until the logic in the program allows it to turn on. It then becomes 'true', and will energize the device that is wired to the respective output.

Zelda A Link Between Worlds Empty Item Slot you can play your favorite online game easily and win real money in the process. Fair Go features a well-designed site that loads fast across various devices. You also get to deposit and withdraw using a wide range of. Link between worlds empty item slot. A common question The Legend of Zelda: A Link Between Worlds players ask is what's the last open item slot for? The final slot is reserved for a quest item that you automatically receive during the. Link between worlds empty inventory slot, link between worlds inventory slots Home › Forums › Link between worlds empty inventory slot, link between worlds inventory slots Public Group active 13 hours, 16 minutes ago.

Live casino slots. If it is used as an internal coil, it will toggle the instructions associated with it. That is, it will close a normally open instruction and open a normally closed instruction.

Allen-Bradley calls these outputs 'OTE', or 'OutpuT Energize'.

An OTE may be used with a hardwired output or an internal coil.

TRUE – A state that indicates an instruction is allowing logic to 'flow' through it.

Also, if the logic in a rung turns on the output of the rung, then the rung is said to be true.

FALSE – Without stating the obvious, this is the opposite of true.

Plc-5

Excerpted from PLC Programming with RSLogix 5000

There are a number of addressing schemes used by PLC manufacturers. Let's take a quick look at how memory locations (including hardware I/O) are accessed with RSLogix 500. Along the way, let's define some terms.

INSTRUCTION – RSLogix's command language is comprised of 'instructions'. An XIC (it looks like a normally open contact –] [– ) is an instruction. A timer is an instruction. A few of the most common instructions are described below.

BIT – an address within the PLC. It can be an input, output or internal coil, among others.

In RSLogix, there are a couple of ways to show the address of a bit. The default is:

[type]:[word]/[bit]

For example, an address that references an output of a MicroLogix 1100 is O:0/0. That is:

O:0/5 means that it is a physical output.
O:0/5 means that it uses Slot 0 (in the case of the 1100, this output is onboard)
O:0/5 means that it is the fifth output on the PLC.

By the way, don't get the capital 'O' confused with a zero.

RUNG – A section of the PLC ladder program that terminates in an output function of some type. Just like in an electrical ladder diagram, a rung has some type of output that is turned on or turned off by the preceding entities in the rung. The first rung in a ladder program is always 0000.

HARDWIRED INPUT – a physical connection to the PLC from an input device (switch or sensor, etc.).

Allen-Bradley uses the capital letter 'I' to designate a hardwired input. An address that describes an input on an SLC 500 is I:4/0.

Similar to the output structure,

I:4/0 means that it is a physical input.
I:4/0 means that it uses Slot 4 (the 5th slot in the rack).
I:4/0 means that it is the first input on the card.

Don't get the capital 'I's' confused with ones.

HARDWIRED OUTPUT – a physical connection from the PLC to an output device (relay or pilot light, etc.) As was said above, an address that references an output of an SLC 500 is O:5/0.

INTERNAL COIL
This is a programmable bit used to simulate a relay within the PLC. The internal coil has no connection to the outside world. It does not connect to an output card. Internal coils are used to store information. The 'contacts' of this 'relay' can then be used multiple times in other parts of the program.

In RSLogix, the 'B3' (binary) file is commonly used for all the internal coils. There are many other words in other files that have bits you can use as internal coils, but we are going to stick with the B3 file for our application.

Plc-5 2 Slot Addressing Machine

B3:0/0 means that it references an internal Binary file
B3:0/0 means that it uses the first word in the table
B3:0/0 means that it is the first bit in the word.

Note that, unlike the Output and Input files, you have to use the file number in the address. In this case, the default file number is 3.

TIMER
A timer is a programmable instruction that lets you turn on or turn off bits after a preset time.

The two primary types of timers are TON for 'timer on delay' and TOF for 'timer off delay'.

Plc-5 2 slot addressing software

Excerpted from PLC Programming with RSLogix 5000

There are a number of addressing schemes used by PLC manufacturers. Let's take a quick look at how memory locations (including hardware I/O) are accessed with RSLogix 500. Along the way, let's define some terms.

INSTRUCTION – RSLogix's command language is comprised of 'instructions'. An XIC (it looks like a normally open contact –] [– ) is an instruction. A timer is an instruction. A few of the most common instructions are described below.

BIT – an address within the PLC. It can be an input, output or internal coil, among others.

In RSLogix, there are a couple of ways to show the address of a bit. The default is:

[type]:[word]/[bit]

For example, an address that references an output of a MicroLogix 1100 is O:0/0. That is:

O:0/5 means that it is a physical output.
O:0/5 means that it uses Slot 0 (in the case of the 1100, this output is onboard)
O:0/5 means that it is the fifth output on the PLC.

By the way, don't get the capital 'O' confused with a zero.

RUNG – A section of the PLC ladder program that terminates in an output function of some type. Just like in an electrical ladder diagram, a rung has some type of output that is turned on or turned off by the preceding entities in the rung. The first rung in a ladder program is always 0000.

HARDWIRED INPUT – a physical connection to the PLC from an input device (switch or sensor, etc.).

Allen-Bradley uses the capital letter 'I' to designate a hardwired input. An address that describes an input on an SLC 500 is I:4/0.

Similar to the output structure,

I:4/0 means that it is a physical input.
I:4/0 means that it uses Slot 4 (the 5th slot in the rack).
I:4/0 means that it is the first input on the card.

Don't get the capital 'I's' confused with ones.

HARDWIRED OUTPUT – a physical connection from the PLC to an output device (relay or pilot light, etc.) As was said above, an address that references an output of an SLC 500 is O:5/0.

INTERNAL COIL
This is a programmable bit used to simulate a relay within the PLC. The internal coil has no connection to the outside world. It does not connect to an output card. Internal coils are used to store information. The 'contacts' of this 'relay' can then be used multiple times in other parts of the program.

In RSLogix, the 'B3' (binary) file is commonly used for all the internal coils. There are many other words in other files that have bits you can use as internal coils, but we are going to stick with the B3 file for our application.

Plc-5 2 Slot Addressing Machine

B3:0/0 means that it references an internal Binary file
B3:0/0 means that it uses the first word in the table
B3:0/0 means that it is the first bit in the word.

Note that, unlike the Output and Input files, you have to use the file number in the address. In this case, the default file number is 3.

TIMER
A timer is a programmable instruction that lets you turn on or turn off bits after a preset time.

The two primary types of timers are TON for 'timer on delay' and TOF for 'timer off delay'.

Timers in A-B SLC and MicroLogix processors use file 4 for their timers.

T4:0 means that it references an internal Timer file
T4:0 means that it uses the first timer in the table

The address T4:0 simply refers to the timer. Each timer has bits that turn on after the timing function is complete. You can address this bit by simply putting a '/DN' after the timer address. DN stands for 'done'.

For example, if timer T4:0 is a TON (timer on delay), then the bit T4:0/DN will turn on after the timer has reached its preset value.

COUNTER
A counter is a programmable instruction that lets you turn on or turn off bits after a preset count has been reached.

There are different types of counters available in the RSLogix, but the CTU (counter up) instruction covers everything we will talk about here.

Counters in A-B SLC and MicroLogix processors use file 5.

C5:0 means that it references an internal Counter file
C5:0 means that it uses the first counter in the table

The address C5:0 simply refers to the counter. Each counter has bits that turn on after the counting function is complete. You can address this bit by simply putting a '/DN' after the counter address. DN stands for 'done'.

For example, if counter C5:0 is a CTU (counter up), then the bit C5:0/DN will turn on after the counter has reached its preset value.

–] [– Normally Open Contact
When used with a hardwired input, this instruction is off until there is a voltage applied to the input. The bit address then goes high, or on, and the instruction becomes 'true.' It works the same way when it has the same address as an internal coil, except that the coil must be turned on by logic in the program.

Allen-Bradley calls these normally open contacts 'XIC', or 'eXamine If Closed' instruction.

An XIC instruction can reference a hardwired input, a hardwired output, an internal coil or a timer done bit, among others.

–]/[– Normally Closed Contact
This is an inverted normally open contact.

When used with a hardwired input, this instruction is 'true' until there is a voltage applied to the input. It then goes low, or off, and becomes 'false.'

It also can be used with an internal coil, becoming true when the coil is off and becoming false when the coil is on.

Allen-Bradley calls these normally closed contacts 'XIO', or 'eXamine If Open' instructions.

-( )- Output Coil
When used with a hardwired output, this function is off until the logic in the program allows it to turn on. It then becomes 'true', and will energize the device that is wired to the respective output.

If it is used as an internal coil, it will toggle the instructions associated with it. That is, it will close a normally open instruction and open a normally closed instruction.

Allen-Bradley calls these outputs 'OTE', or 'OutpuT Energize'.

Plc-5 2 Slot Addressing Machines

An OTE may be used with a hardwired output or an internal coil.

TRUE – A state that indicates an instruction is allowing logic to 'flow' through it.

Also, if the logic in a rung turns on the output of the rung, then the rung is said to be true.

FALSE – Without stating the obvious, this is the opposite of true.

Excerpted from PLC Programming with RSLogix 500





broken image